How to Select Surge Arresters for 11kV, 24kV and 33kV Overhead Lines
Publish Time: 2026-08-24 15:42:33 Author: DELIXI
Ask an engineer how they picked the surge arrester for a pole-mounted transformer and the answer is usually the system voltage. An 11 kV line gets an "11 kV arrester." A 33 kV line gets a "33 kV arrester."
That single step skips the two parameters that actually determine whether the arrester survives — continuous operating voltage (Uc) and rated voltage (Ur) — both of which depend on how the network neutral is earthed, not just on the line voltage. Get them too low and the arrester heats up under temporary overvoltage and fails, often taking the feeder out with it. Get them too high and the protective level rises, leaving the transformer exposed to the surge you installed the arrester to stop.
And even when the calculation is right, a two-metre connection lead can quietly cancel a third of the protection.
This guide works through the selection in seven steps for 11 kV, 24 kV and 33 kV overhead distribution, with the full rating tables you need to specify a part number.
What a metal-oxide arrester actually does
A modern gapless arrester is a stack of zinc-oxide varistor blocks with a strongly non-linear voltage/current characteristic. At normal operating voltage it conducts a leakage current in the region of a milliamp and behaves as an insulator. When a lightning or switching surge arrives, its resistance collapses by orders of magnitude, it conducts the surge current to earth, and it clamps the terminal voltage at its residual voltage — then returns to the high-resistance state as the surge passes, without any follow current for the system to interrupt.
Three practical consequences:
The arrester is continuously energised. It must tolerate normal operating voltage for 30 years without thermal runaway. That is the Uc requirement.
It must survive temporary overvoltage (TOV) during earth faults, which on some networks lasts hours rather than cycles. That is the Ur requirement.
It clamps, it does not eliminate. The protected equipment sees the residual voltage plus whatever the connection leads add. That is the protective margin question.
The product standards to quote in a specification are IEC 60099-4 for the arrester itself and IEC 60099-5 for selection and application.
Step 1: Set Uc from the system voltage and the neutral earthing
Continuous operating voltage (Uc) must exceed the highest continuous power-frequency voltage that will appear across the arrester, phase to earth:
Uc ≥ Us ÷ √3
where Us is the highest system voltage — 12 kV for an 11 kV network, 24 kV for a 22 kV network, 36 kV for a 33 kV network. That is the floor. Whether you can sit near it depends on Step 2.
Add margin where the network runs above nominal voltage, where voltage regulation is poor, or where harmonic distortion is significant.
Step 2: Set Ur from temporary overvoltage — this is where neutral earthing decides everything
During a single phase-to-earth fault, the two healthy phases rise. How far, and for how long, is entirely a function of the neutral arrangement — and this is the step most commonly skipped.
Neutral arrangement
Earth fault factor
Fault duration
Typical Ur selection
Effectively (solidly) earthed
≈1.4
Cleared in seconds by protection
Ur ≈ 0.75–0.8 × Us
Low-resistance earthed
1.4–1.7
Seconds
Ur ≈ 0.8–1.0 × Us
Isolated / resonant (Petersen coil) earthed
up to 1.73
Can persist for hours
Ur ≥ Us
On an isolated or resonant-earthed 33 kV network — common in rural distribution across much of Asia, Africa and Latin America — a sustained earth fault puts close to full phase-to-phase voltage across the arresters on the healthy phases, potentially for the rest of the shift. An arrester chosen on the "0.8 × Us" rule for a solidly earthed system will cook.
This is why our range offers several Ur values inside each voltage class rather than one. Confirm the neutral earthing arrangement before selecting a part number — it is the single most valuable line in an RFQ.
Step 3: Choose the discharge class — 5 kA or 10 kA
Nominal discharge current (In) defines the 8/20 µs current at which residual voltage is specified and, together with the long-duration ratings, describes how much energy the arrester can absorb.
5 kA (YH5W)
10 kA (YH10W)
2 ms square wave withstand
150 A
250 A
4/10 µs high current withstand
65 kA
100 kA
Typical use
Distribution transformers, branch lines, moderate lightning activity
High ground flash density, substation entries, cable transitions, higher-value transformers, long exposed feeders
The price difference between the two classes is modest against the cost of a failed 315 kVA transformer and a day of crew time. On feeders in high-keraunic regions, or where the arrester also has to handle switching and cable-discharge energy, the 10 kA class is the defensible choice.
Step 4: Check the protective margin
The lightning impulse protective level (Upl) is the residual voltage at nominal discharge current, 8/20 µs. The protected equipment has a lightning impulse withstand level (LIWL/BIL). The margin between them is what you are buying:
Protective margin (%) = (LIWL − Upl) ÷ Upl × 100
A margin of at least 20 % is the usual minimum, and more is preferred because the margin erodes in service (Step 5).
Worked from our published residual voltages against typical transformer insulation levels:
Class
Arrester
Upl (8/20 at In)
Typical transformer LIWL
Margin
11 kV
YH5W-12/36
36 kV
75 kV
~108 %
24 kV
YH5W-24/72
72 kV
125 kV
~74 %
33 kV
YH5W-36/108
108 kV
170 kV
~57 %
Note the trend: margin shrinks as voltage class rises. At 33 kV there is far less room for error than at 11 kV, which makes the next step disproportionately important on 33 kV lines.
Step 5: Lead length — the field error that undoes the calculation
The transformer does not see Upl. It sees Upl plus the inductive voltage developed along the connection leads on both the line side and the earth side.
Conductor inductance is roughly 1 µH per metre. A 10 kA 8/20 µs surge has a rate of rise in the order of 1.25 kA/µs, so each metre of lead contributes approximately:
ΔV ≈ 1 µH/m × 1.25 kA/µs ≈ 1.25 kV per metre
Four metres of total lead — two metres up to the line connection, two metres down to the earth — adds around 5 kV to what the transformer experiences. On a 33 kV installation with Upl of 108 kV that is a 5 % erosion. On an 11 kV installation with Upl of 36 kV it is closer to 14 %, and careless routing of 3–4 m on each side can eat a quarter of the protection you paid for.
Four rules for the crew:
Mount the arrester as close to the transformer bushing as physically possible.
Keep both leads short and straight. No loops, no service coils, no generous slack "for later."
Bond the arrester earth lead directly to the transformer tank, and take the tank and the arrester to the same earth electrode. The transformer insulation is stressed by the difference between its terminal and its tank — connecting them at the same point removes the lead drop from that difference.
Verify earth electrode resistance against the local standard; a low protective level into a poor earth is a partial solution at best.
Step 6: Housing, creepage and pollution
Composite (silicone-housed) arresters dominate modern distribution work for reasons that go beyond price:
Composite / polymer
Porcelain
Failure mode
Splits and vents; does not shatter
Can fragment under internal fault pressure
Weight
Light, one-hand installation
Heavier
Pollution performance
Hydrophobic surface, recovers between wetting cycles
Requires washing in severe sites
Vandalism / transit damage
Impact tolerant
Brittle
Creepage follows the same pollution logic as any other outdoor MV component — roughly 16 mm/kV in light pollution, 20 mm/kV medium, 25 mm/kV heavy and 31 mm/kV very heavy per the IEC 60815 classes. Coastal, desert and heavy-industry routes need the extended-creepage version specified at tender, not discovered at year two. The same reasoning that governs your drop-out fuse cutouts and composite insulators applies here — specify the whole pole to one pollution class, not component by component.
Step 7: Disconnector, position and mounting
Grounding-lead disconnector. If an arrester fails, it fails to earth — and without a disconnector that becomes a permanent earth fault that keeps the feeder out. A disconnector releases the earth lead when the arrester fails, restoring service and leaving a hanging lead that a crew can spot from the ground. On radial rural feeders this single accessory pays for itself the first time it operates. Confirm whether your quoted units include one.
Where to install on the feeder:
At every distribution transformer, on the HV bushings
At overhead-to-cable transitions, at both ends of the cable section
At line terminations and open points
At riser poles and at the entry to switching equipment
On both sides of a normally open sectionaliser where the line may be back-fed
Mounting. Confirm bracket type, phase spacing and clearance to the pole and to the drop-out fuse cutout mounted alongside, and match hardware corrosion protection to the rest of the power fittings on the structure.
Full rating reference: 11 kV, 24 kV and 33 kV
All values are published data for our composite zinc-oxide range. Residual voltages are given for 1/4 µs steep front, 8/20 µs lightning and 30/60 µs switching impulses.
Reading the model code: YH5W-24/72 is a 5 kA metal-oxide arrester with 24 kV rated voltage and 72 kV residual voltage at nominal discharge current. YH10W is the 10 kA class equivalent.
Five mistakes that shorten arrester life
Selecting on system voltage alone. Without the neutral earthing arrangement, Ur is a guess.
Under-rating Ur on an isolated-neutral network. A fault that persists for hours is a thermal duty, not a transient.
Long connection leads. The most expensive arrester on the market cannot outrun four metres of inductance.
Separate earths for arrester and transformer tank. This puts the lead drop directly across the transformer insulation.
Omitting the disconnector on radial feeders. One failed arrester then equals one feeder outage until a crew locates it.
What to include in your RFQ
Nominal and highest system voltage (Us)
Neutral earthing arrangement and expected earth-fault clearing time
Required Ur and Uc, if already calculated — or send us the above and we will calculate
Site altitude, ambient temperature range and lightning ground flash density if known
Quantities, delivery schedule and destination port
Datasheets, structure drawings and test certificates are available from our Download centre and Certificates pages.
FAQ
What is the difference between Uc and Ur on a surge arrester? Uc is the continuous operating voltage the arrester can withstand indefinitely; Ur is the rated voltage, defined by its ability to survive temporary overvoltage for a specified duration. Uc sets the everyday duty, Ur sets the fault-condition duty.
How do I choose the arrester rated voltage for an 11 kV line? Start from Uc ≥ 12 ÷ √3 ≈ 6.9 kV, then set Ur from the neutral earthing: roughly 0.8 × Us on an effectively earthed system, and at least equal to Us on an isolated or resonant-earthed system.
Should I use a 5 kA or a 10 kA arrester? 5 kA is standard for distribution transformers in moderate lightning conditions. Choose 10 kA for high ground flash density, cable transitions, substation entries and higher-value assets — it carries the higher long-duration and high-current withstand.
How long can the arrester connection leads be? As short as practical. Each metre adds roughly 1.25 kV to the voltage the equipment sees during a 10 kA surge, so keep the line and earth leads combined to a metre or two and bond the earth lead directly to the transformer tank.
Does a surge arrester replace a drop-out fuse? No. They address different faults. The arrester limits overvoltage; the drop-out fuse cutout interrupts overcurrent and provides visible isolation. A pole-mounted transformer normally has both.
Composite or porcelain housing? Composite for most modern distribution work — lighter, safer failure mode, better under pollution and vandalism. Porcelain remains viable where utility practice and inland conditions favour it.
Send us your line data and we will size the arresters
Give us system voltage, neutral earthing, transformer schedule and site conditions, and we will return Ur, Uc, discharge class and part numbers with datasheets — coordinated with the cutouts, insulators and fittings on the same structure.
This website uses cookies so that we can provide you with the best user experience possible. Cookie information is stored in your browser and performs functions such as recognising you when you return to our website and helping our team to understand which sections of the website you find most interesting and useful.
Strictly Necessary Cookies
These cookies are essential to provide you with services available through our website and to enable you to use certain features of our website.
Without these cookies, we cannot provide you certain services on our website.
If you disable this cookie, we will not be able to save your preferences. This means that every time you visit this website you will need to enable or disable cookies again.
Tracking cookies
These cookies are used to collect information to analyze the traffic to our website and how visitors are using our website.
For example, these cookies may track things such as how long you spend on the website or the pages you visit which helps us to understand how we can improve our website for you.
The information collected through these tracking and performance cookies do not identify any individual visitor.
Please enable Strictly Necessary Cookies first so that we can save your preferences!
Targeting and advertising cookies
These cookies are used to show advertising that is likely to be of interest to you based on your browsing habits.
These cookies, as served by our content and/or advertising providers, may combine information they collected from our website with other information they have independently collected relating to your web browser's activities across their network of websites.
If you choose to remove or disable these targeting or advertising cookies, you will still see adverts but they may not be relevant to you.
Please enable Strictly Necessary Cookies first so that we can save your preferences!
Cookie Policy
Your privacy is important to us
Cookies are very small text files that are stored on your computer when you visit a website. We use cookies for a variety of purposes and to enhance your online experience on our website (for example, to remember your account login details).
You can change your preferences and decline certain types of cookies to be stored on your computer while browsing our website. You can also remove any cookies already stored on your computer, but keep in mind that deleting cookies may prevent you from using parts of our website.
Contact us!×
We're not around but we still want to hear from you! Leave us a note: