CDCE 9 series low voltage capacitor compensation device in low voltage power capacitor as the main body, the software and hardware technology, micro sensor technology, microelectronics miniature network technology and electrical appliance manufacturing technology such as the latest technological achievements, the intellectualization, realizing the low voltage reactive power compensation function and convenient for, protection, measurement, signal, online, etc. Series of functions, is a breakthrough of the low voltage reactive power automatic compensation technology, flexible use in low voltage reactive power compensation of various occasions, to change the structure of the existing low voltage reactive power compensation equipment and automaticmode.
Applications
Local reactive power compensation
The power supply cabinet is flexible and convenient to use, and can be used without special boxes, cabinets, and without additional controllers. This capacitor compensation cabinet can realize small-capacity reactive power automatic compensation in various occasions, and the effect is ideal.
In box substation
In box substation, it is assembled into the reactive power automatic compensation device with block type, or combined with the integrated measurement and control device of the distribution transformer, it is assembled into the distribution inspection and measurement system and the reactive power automatic compensation system, which occupies little space, is easy to install, easy to maintain and adjust the capacity.
In new outdoor distribution transformer JP cabinet
It is applied to the reactive power automatic compensation of the 0.4kV voltage feeder terminal. Small size, better use of the space of the JP cabinet.
In low-voltage switchgear
The products are assembled in the cabinet and form areactive power automatic compensation device, which breaks the structural mode of the existing reactive power automatic compensation device. The compact size , the same cabinet can compensate for more capacity, easy installation, convenient maintenance, each intelligent. The operating condition indication and display on the capacitor allows manual retraction of a single unit without the need for additional manual operation.
CDCE 9 series low voltage capacitor compensation device in low voltage power capacitor as the main body, the software and hardware technology, micro sensor technology, microelectronics miniature network technology and electrical appliance manufacturing technology such as the latest technological achievements, the intellectualization, realizing the low voltage reactive power compensation function and convenient for, protection, measurement, signal, online, etc. Series of functions, is a breakthrough of the low voltage reactive power automatic compensation technology, flexible use in low voltage reactive power compensation of various occasions, to change the structure of the existing low voltage reactive power compensation equipment and automaticmode.
GGD-CDCE9 series low-voltage intelligent capacitor compensation device has the characteristics of flexible compensation mode, good compensation effect, small size, low power consumption, convenient installation and maintenance, long service life and high reliability, which can meet users’ fine requirements for reactive power compensation to improve power factor, improve power quality and energy saving loss.
Product Features
Intelligent network
This product is a main control type product, which can realize active control of the product without additional controller.
Self-test self-regulation
Total compensation priority optimization
Operating passing zero
Synchronous switching s witching, voltage zero – crossing input, current zero – crossing cutting, switching no inrush current.
Explosion-proof patent
Product built-in explosion-pro of devic e, high reliability.
Invention patent: CN201510299889.2
CN201520376876.6
Small size
The product is small, sta ndardized and modular.
■ For example: GGD-CDCE9-450/10.10, Dimensions:W80mm * L360mm * H272mm
Nine protections
■ The product has 9 protection functions: undervoltage protection, overvoltage protection, undercurrent protection, overcurrent protection, unbalance protection, power failure protection, Phase loss protection, capacitor discharge protection, over temperature protection.
■ Safe, reliable, and meticulous
Easy maintenance
■ LCD display Chinese display protection action type;
■ Smart capacitors have self-diagnostics;
■ The fault content is reflected on the LCD screen, which is good for on-site fault finding;
■ Capacitor damage requires a simple and quick replacement of the unit.
Selection Guide
Product name
Compensation method
Control mode
Capacitor rated voltage
Rated capacity (kvar)
GGD-CDCE9
S
A
0450
0505
S:Three-phase compensation
A.Automatic contro
Common compensation: 0450:450V (Line voltage)
Common compensation: 0505:5+5kvar 1005:10+5kvar 1010:10+10kvar 1515:15+15kvar 2020-20+20kvar
When selecting the type, the special specification capacity can be negotiated.
Common compensation products, 5-40kvar other capacity can be customized.
Split compensation products, other capacity within 5-30kvar can be customized.
Communication line ordering coding rule
The communication line is used for communication between two adjacent smart capacitors in the same network (cabinet). The communication line is an 8-core conventional network cable. The product body comes with a 20cm network cable. Customers can customize it if they need other sizes.
Product name
Communication line
Length
Remark
GGD-CDCE9
20
L:Communication line
20:Length 20cm 70:Length 70cm 300:Length 300cm
Standard for ontology products Optional Optional
Secondary transformer order coding rules
When the product is used as active control for reactive power com pensation, the secondary curren t transformer for sampling must be configured. (≤ 20 units)
The secondary current transformer is used for current sampling , and the secondary current (0-5A) of the primary current transformer of the incoming line cabinet is again converted. It is a (0~5mA) current signal.
A system of secondary transformers with one:
Only a total complemented network system is equipped with a single-hole secondary current transformer;
The networking system with sub-compensation is equipped with a three-hole secondary current transformer.
This accessory is not required when networked with an external controller(JKGPJ).
Product name
Current sampling hole numbe
CT
Remark
GGD-CDCE9
1
CT
1:Single hole 3:Three hole
CT.secondary current transformer
Three-phase co-compensation scheme for active control of products Three-phase mixing scheme for active control of products
Hole diameter: φ5mm
External controller-JKGPJ
■ This product is an integrated controller for reactive power compensation and power distribution monitoring. It integrates data acquisition, communication, reactive power compensation, grid parameter measurement, analysis and other functions.
■ Using RS485 communication mode, it can be used as external controller to communicate with up to 31 GGD-CDCE9 products.
■ Standard one-meter 3 meter communication line (one end RJ11 interface, one end RJ45 interface)
JKGPJ controller
Product name
Voltage
Function option
JKGPJ
M
Z
M:220V
Z:Communication control 31 circuit
Technical parameter
Standard
JB/T 9663
Sampling voltage (V)
3*220V±20%
Sampling current (A)
≤5A
Sensitivity
≤200mA
Action error
≤±2.0%
Clock error
<1s/d
Power consumption
≤2VA
Control smart capacitor
S31 pcs
Protection degree
IP30
Overall and Installation Dimensions (mm)
Product Specifications
Working conditions
■ Ambient temperature (normal condition): -25°C 〜40°C
■ Storage temperature: -25 C – 55°C (within 24h, up to 70°C )
■ Altitude: < 2000m
■ Relative humidity: 40°C , 20% – 90%
■ Rated voltage (common compensation): AC400
■ Rated voltage (split compensation): AC230
■ Voltage deviation: ± 20%
■ Voltage waveform: sine wave, the total distortion rate is not more than 5%
■ Working frequency: 50Hz soil 1.5Hz
Reactive power compensation parameter
■ Switching structure: synchronous switch
■ Capacitor switching in terval: ≤ 0s~180s (can be set)
■ Network connection: online ≤ 20 sets
Error requirement
■ Voltage measurement: ≤ 0.6%
■ Current measurement: ≤ 1.0%
■ Power measurement: ≤ 2.5%
■ Power factor measurement: ± 0.01
■ Temperature measurement: ± 1°C
Product performance
■ Over temperature protection: 40°C -80°C adjustable (factory setting is 80°C )
■ Switching inrush current: ≤ 3ln
■ Withstand voltage shock: ≥ AC3500V (DC5000V)
■ Operation noise: ≤ 70dB (A sound level)
■ Power consumption: Standby ≤ 4VA (led)
■ Control accuracy: 100%
■ lake and cut allowed times: 1 million times or more (with load)
■ Annual failure rate: ≤ 0.1%
Standard
■ Standard: GB/T 15576
■ Certificate: CCC
Product parameters
Controller function
Common compensation
Split compensation
Protective function
Undervoltage protection
■
Overvoltage protection
■
Undercurrent protection
■
Overcurrent protection
■
Unbalance protection
■
Power failure protection
■
Phase-break protection
■
Capacitor discharge protection
■
Over temperature protection
■
Setting function
Factory setting
Setting range
Factory setting
Setting range
Capacitance capacity setting
Nominal value
1-40 (kvar
Nominal value
1-40 (kvar)
nput threshold Setting
0.95
0.90-0.98
0.95
0.90-0.98
Switching delay setting
10s
0-180s
10s
0-180s
Primary CT ratio setting (n:1)
100
1-999
100
1-999
Communication address setting,255 is automatic networking
-No this option ■ Standard 1. The temperature means that when the internal temperature of the product exceeds the set value during the use, the product will automatically exit the operation, which can effectively protect the product, and the customer can adjust according to their actual use requirements.(40°C ~80°C )
Controller display and function
LCD type common compensation operation interface
LCD type split compensation operation interface
Overall and Installation dimensions
Common-compensation — Installation and dimensions
Split-compensation 一 Installation and dimensions
Product installation and dimensions (mm)
Specifications
nstallation dimensions
Overall Dimensions
Compensation method
Material No
Description
A
B
D
E
F
C(Length)
G(Width)
H(height
Three-phase commoncom pensatio
GGD-CDCE9SA04500505
GGD-CDCE9-SA450/5.5
110
93
7
10
291
80
360
222
GGD-CDCE9SA04501005
GGD-CDCE9-SA450/10.5
272
GGD-CDCE9SA04501010
GGD-CDCE9-SA450/10.10
GGD-CDCE9SA04501515
GGD-CDCE9-SA450/15.15
GGD-CDCE9SA04502020
GGD-CDCE9-SA450/20.20
322
Split Phase compensation
GGD-CDCE9FA02500005
GGD-CDCE9-FA250/5
80
360
222
GGD-CDCE9FA02500010
GGD-CDCE9-FA250/10
272
GGD-CDCE9FA02500015
GGD-CDCE9-FA250/15
GGD-CDCE9FA02500020
GGD-CDCE9-FA250/20
GGD-CDCE9FA02500030
GGD-CDCE9-FA250/30
322
Product installation instruction
Terminal definition and arrangement diagram
Power line connection
1. The power line selects multi-core copper conductors with appropriate cross-sectional area according to the total capacity of the product. Capacitors with a total capacity of 40kvar or more should adopt multi-core copper conductors with a cross-section of 16mm², and otherspecifications can use multi-core copper conductors of 10mm²;
2. Attention: When connecting the power line, you must select the copper wire of the corresponding specification, tighten the screw, and pull the power cord firmly to ensure that the connection is very firm before use, otherwise the terminal will be excessively heated, which will eventually lead to product damage. The sub-compensated smart capacitor must be connected to the neutral line, and the wire diameter specification is the same as the three-phase power supply.
Signal line connection
1. The secondary current signal line is connected by a network cable;
2. The RS485 communication line adopts the plug-in connection of the network cable, and the two smart capacitors can be directly connected by the communication line accessories
Indicator terminal wiring
If the user has the requirements for the output capacitor status indicator, the external indicator can be as follows:
1. Common compensation: C1 (terminal) and C2 (terminal) are the active signal output terminals of the two sets of capacitor switching status indicators. The C1 and C2 outputs are connected to one end of two AC 380V indicators, and the other end of the indicator light. Connect to phase B (or phase C).
2. Split-compensation : Ca (terminal), Cb (terminal), Cc (terminal) are the active signal output terminals of the threephase capacitor switching status indicator of the supplementary A, B and C. Ca, Cb, and Cc are connected to one end of three AC 220V indicators, and the other end of the indicator is connected to the common terminal (N).
Current transformer wiring Primary CT installation position
Secondary CT installation
1) Common compensation Pass the B-phase primary CT output line through the single-hole secondary CT configured by the company, and the secondary CT outputs a terminal cable port. When multiple networked networks are running, only the secondary CT needs to be connected to the host, and the slave only needs to be connected to the host through the network cable;
2) Split-compensation The A-phase, B-phase, and C-phase primary CT output lines are respectively passed through the three-hole secondary CT configured by the company, and the secondary CT output end is connected to the network cable port. When multiple networked networks are running, only the secondary CT needs to be connected to the host, and the slave only needs to be connected to the host through the network cable.
WARNING: Primary CT sampling (7A1A, TA1B, TA1C) should be installed in front of the capacitor and load in front of the contact (at the bus), and pay attention to the phase sequence.
Ground wire connection There is a grounding mark at the grounding wire. The grounding wire is a copper wire with a cross-sectional area of not less than 2.5 mm². The grounding must be reliable and connected to the external grounding terminal.
Product application wiring diagram
Single unit common compensation wiring diagram (single unit local compensation 1)
List: (For example: common compensation of 40kvar)
Product
Material No.
Description
GGD-CDCE9 three-phase common-compensation *1
GGD-CDCE9SA04502020
GGD-CDCE9-SA450/20.20
GGD-CDCE9 single hole secondary CT*1
GGD-CDCE91CT
GGD-CDCE9 single hole secondary CT
Single Split-compensation wiring diagram (single unit local compensation 2)
This website uses cookies so that we can provide you with the best user experience possible. Cookie information is stored in your browser and performs functions such as recognising you when you return to our website and helping our team to understand which sections of the website you find most interesting and useful.
Strictly Necessary Cookies
These cookies are essential to provide you with services available through our website and to enable you to use certain features of our website.
Without these cookies, we cannot provide you certain services on our website.
If you disable this cookie, we will not be able to save your preferences. This means that every time you visit this website you will need to enable or disable cookies again.
Tracking cookies
These cookies are used to collect information to analyze the traffic to our website and how visitors are using our website.
For example, these cookies may track things such as how long you spend on the website or the pages you visit which helps us to understand how we can improve our website for you.
The information collected through these tracking and performance cookies do not identify any individual visitor.
Please enable Strictly Necessary Cookies first so that we can save your preferences!
Targeting and advertising cookies
These cookies are used to show advertising that is likely to be of interest to you based on your browsing habits.
These cookies, as served by our content and/or advertising providers, may combine information they collected from our website with other information they have independently collected relating to your web browser's activities across their network of websites.
If you choose to remove or disable these targeting or advertising cookies, you will still see adverts but they may not be relevant to you.
Please enable Strictly Necessary Cookies first so that we can save your preferences!
Cookie Policy
Your privacy is important to us
Cookies are very small text files that are stored on your computer when you visit a website. We use cookies for a variety of purposes and to enhance your online experience on our website (for example, to remember your account login details).
You can change your preferences and decline certain types of cookies to be stored on your computer while browsing our website. You can also remove any cookies already stored on your computer, but keep in mind that deleting cookies may prevent you from using parts of our website.
Contact us!×
We're not around but we still want to hear from you! Leave us a note: