+86 13587807973

Power Substation

  • LW8-33kV HV SF6 Circuit Outdoor Breaker
  • LW8-33kV HV SF6 Circuit Outdoor Breaker

LW8-33kV HV SF6 Circuit Outdoor Breaker

The 33kv outdoor circuit breaker is a kind of 3 phase AC 50Hz outdoor type breakers. The gas of the SF6 is employed as the arc-extinguishing medium and the dielectric material.

The 33kv outdoor circuit breaker is a kind of 3 phase AC 50Hz outdoor type breakers. The gas of the SF6 is employed as the arc-extinguishing medium and the dielectric material.lt uses the structure of pneumatic arc.extinguishing chamber, and the breaking performance is excellent. It can be widely used in the electrical system whose rated voltage is 33kV to control the rated current and short-circuit current.connect the breaker and cut the current in capacitor banks The current transformers inside are used for measuring and protecting the breaker.The LW8-33 breaker is the regenerate type of oil type breaker.

33kv outdoor circuit breaker manufacturers

Meaning of Type

outdoor breaker manufacturers

Characteristic of Structure

The outdoor breaker has the characteristics of small, outdoor type and with the console pot structure. It can match with CT 14 spring operation mechanism. The spring operation mechanism associates with the main body, so the installation and debugging are convenient.Also it can be operated frequently and the mechanical life is not less than 3000 times.

The hv breaker uses pneumatic arc-extinguishing chamber.so the breaking performance is excellent.The 40kA accumulative breaking times can reach to 12.

The seal performance is reliable.The breaker uses imported sealed rubber insert.The dynamic seal uses structure of V shape grommet with spring pressure.

The secondary terminal block is offered by the manufacturer as a set with the breaker to make sure that the annual leak rate of SF6<0.5%.


The iron core of the inner current transformer is made of materials with the performance of crystallite(alloy)high conduction magnetic. So the accuracy class can reach up to 0.2 or 0.2S.12 pieces of current transformers can be used inside as the clients’requirement. And it will not re-burn when switch zero load for 50kms.

Technical Data

NoltemUnitValue
1Rated voltagekV40.5
2Rated insulation levelThunder impulse withstand (Full peak valueskV185/215(Interrupter)
Power frequency withstand voltage(1 minkV95
3Rated currentA16002000
4Mechanical levelTimes3000
5Rated SF6 pressure (20℃MPa0.45
6Locking pressure (20℃)MPa0.45
7Minimum operating ambient temperature~30
8Rated short-circuit breaking currentKA2531.5
9Rated short-circuit makingg current(peak)KA6380
10Rated short time withstand current (thermal stability current)KA2531.5
11Rated short time withstand current (dynamic stability current)KA6380
12Rated out of phase breaking currenKA6.380
13Rated short-circuit durationS4
14Switch-on time (rated operating voltageS≤1
15Switch-off time (rated operating voltageS≤0.07
16Rated operating sequenceCO-0.3S-CO-180S-CO
17Rated switching single capacitor bank currentA400
18Cumulative breaking times of rated short-circuit breaking currentTimes1510
19Annual leakage rate%/Year≤1
20SF6 water content (VV)PPmV≤150
21Rated operating voltage matching with CT14 spring operating mechanismV~220
Switch-on/off coil voltageVAC;220
DC:110  220
Energy storage motor voltageVAC;220
DC:220
22Weight of Sf6kg8
23Weight of breaker(including operating mechanism)kg1400