+86 13587807973

Distribution Transformer

  • S11-24kV Series Hermetically-sealed Distribution Oil Immersed Transformer
  • S11-24kV Series Hermetically-sealed Distribution Oil Immersed Transformer
  • S11-24kV Series Hermetically-sealed Distribution Oil Immersed Transformer
  • S11-24kV Series Hermetically-sealed Distribution Oil Immersed Transformer

S11-24kV Series Hermetically-sealed Distribution Oil Immersed Transformer

The hermerically-sealed oil-immersed distribution transformer is widely used in the power distribution system. 

The hermerically-sealed oil-immersed distribution transformer is widely used in the power distribution system. Owning to the elasticity of shell, it could adapt the inflation of the oil when under high temperature.

Model designation

Working condition

  • Installation mode: indoor/ outdoor/ type.
  • Highest ambient temperature should not over +40°C; highest daily average temperature should not over +30 °C .
  • Highest annual average temperature should not over +20°C , lowest temperature should not below-25’C .
  • Highest altitude: 1000m

* We can supply the transformers which operate in special operating conditions according to use’s requirements.

Reference standards

1 .Power transformer: GB1094.1-2-1996, GB1094.3-2003, GB1094.5-2008

2. Three-phase oil-immersed transformers: GB/T6451-2008

Performance characteristics

1 .A multilayer cylinder structure is used for all high voltage windings in order to improve the voltage impulse distribution of windings.

2. For the capacity range of low voltage windings is from 30KVA to 2000KVA,the cylinder type or spiral structure is used to ensure the high mechanical strength, ampere lure distribution, and excellent short-circuits proof performance.

3.The securing structure is set in the transformer body, which is used for ensuring that no displacement will occur during the transportation;meanwhile, the turnbuckles are mounted in fasteners, which is for assuring that fasteners will not be loose during the long term operation.

4. Corrugated tanks are used in the transformer for replacing the conservator. The tank enclosure and rim are completely sealed by welding or bolting up, which prolongs the service life of transformer oil.

5. The oil immersed power transformer surface are painted with primer and finish coats after degreasing, derusting, and phosphorizing; which can meet the special operation requirements in metallurgic and petrochemical industries, as well as, in moist and dirty places.

6. The press relief valves, signal thermometers, and gas relays are equipped in the oil tank of hermetically sealed transformer in order to the standard requirement for safe operation.

The amorphous metal distribution transformer are attractive and competitive due to the compact shape, excellent design, and maintenance-free.

7.Power transformer:

S9 No-loaded losses, Load-loss comply with GB/ T6451-2008

510 No-loaded losses is lower 10% than GB/T6451 -2008Load-loss is lower 5% than GB/T6451-2008

511 No-loaded losses is lower 20% than GB/T6451-2008 Load-loss is lower 5% than GB/T6451-2008

Technical parameters of S11-M—50 1600/24 series distribution transformers

Rated capacity (kVA)Voltage combination (kV)Connec
ting
group
No-load
loss
y (w)
Load-loss
(W)(75℃)
Short ciruit
impedance
(%)
No-load
current
(%)
Weight (kg)Overail dimension (mm)Gauge
(mm)
High
voltage
(kV)
Tapping
(%)
Low
voltage
(kV)
TareOilTotalLength x
Width * Height
5024±5%
±2×2.5%
0.4Dyn11
YynO
1308704.02.03301806301000x730x1350400X400
8018012501.84102208201040x780x1390400X400
10020015001.64602409301060x790x1440550×550
12524018001.5530270108010B0x800x1480550×550
16029022001.462029011601290x760x1530550×550
20033026001.369031012801340x790x1540550×550
25040030501.280036014001420x830x1550550×550
31548036501.190040015501480x880x1570550×550
40057043004.51.0111050019101660x980x1590660×660
50068051501.0132057022201700x1000x1660660×860
63081062000.9158067026201750x1010x1800820×820
80098075000.8189074030401810x1040x1860820×820
10001150103000.7204080032801830x1060x1940820×820
12501360120000.6236091037901950x1170x2080820×820
16001640145000.52980110047701890x1180x2370820×820
CONTACT US
Copyright © 2007-2024 Delixi Electric All Rights Reserved.    浙ICP备13001006号-1  浙ICP备13001006号-3  Sitemap

LEAVE A MESSAGE

Contact us!
We're not around but we still want to hear from you! Leave us a note:

* indicates a required field