Suitable for high-rise buildings and large crowd gathering areas; For example: government, government agencies, schools, supermarkets, etc; Special industrial accident sites (industrial and mining transportation), civil defense underground transportation facilities, chemical, steel, large-scale processing centers, etc., provide dedicated power supply for emergency equipment.

product details

product namerated powerInstallation methodmodeloutput circuit
YJ-D
2P2:2.2KVA


160:160KVA

G: Cabinet type

Z: Host
30: Emergency time of 30 minutes
90: Emergency time of 90 minutes
120: Emergency time of 120 minutes

3: 3 circuits

10: 10 circuits
Rated power (kVA)Installation methodOrder code
2.2Cabinet typeYJD2P2G O *
3.7Cabinet typeYJD3P7G O *
5.5Cabinet typeYJD5P5G O *
7.5Cabinet typeYJD7P5G O *
11Cabinet typeYJD11G O*
15Cabinet typeYJD15G O *
18.5Cabinet typeYJD18P5G O *
22Cabinet typeYJD22G O*
30Cabinet typeYJD30G O *
37Cabinet typeYJD37G O *
45Cabinet typeYJD45G O *
55Cabinet typeYJD55G O *
75Cabinet typeYJD75G O *
93Cabinet typeYJD93G O *
110Cabinet typeYJD110G O *
132Cabinet typeYJD132G O *
160Cabinet typeYJD160G O *

Note: “O” in the ordering code represents emergency time

In the ordering code, “*“

Indicating output circuit

P represents the decimal point

When using the host: without battery

When equipped with emergency time: including corresponding batteries

Product parameters

modelYJ-D
AC outputrated powerKVA2.2~160
output accuracyV380±5%
emergency frequencyHz50±0.25
Input VoltageV±20%
input frequencyHz50±5%
emergency timemin≥ 90 (standard type)
conversion timeS<0.25
noisedB≤55
temperature90
insulation resistance≥5
pressurizationV/1min1500
wave formsine wave
protectOverload, short circuit, undervoltage protection
TypeValve controlled maintenance free lead-acid batteries
displayLCD、LED
efficiency≥ 99% (when powered by mains power); 290% (during emergency power supply)
Overload capacity120% instantaneous overload
Applicable loadLighting category
Execution standardsGB/T 17945
authentication certificateCCC